As the North American energy storage market continues to expand, the safety compliance of stationary Energy Storage Systems (ESS) has drawn increasing attention from regulators, insurers and end users. As a joint U.S.-Canadian national standard, UL 1973:2022 enjoys high industry recognition and serves as a critical compliance threshold for energy storage products entering the U.S. and Canadian markets.
The 3rd edition of ANSI/CA/UL 1973 was officially released on February 25, 2022. The new version includes multiple major updates: newly added test requirements for sodium-ion batteries and metal-air batteries, introduction of Functional Safety assessment, and additional EMC provisions, further raising the safety entry barriers for ESS in North America.
The standard divides assessment into four major modules: Electrical Safety, Mechanical Safety, Environmental Reliability, and Functional Safety Evaluation, forming a complete safety evaluation matrix for energy storage batteries.
表格
| Test Item | Test Purpose | Pass Criteria |
|---|---|---|
| Overcharge Test | Verify tolerance under overcharge conditions | No fire, no explosion, no leakage |
| External Short Circuit Test | Simulate external fault and verify protection effectiveness | No fire or explosion; enclosure temperature within limits |
| Overdischarge Protection Test | Verify reliability of overdischarge protection | Protection activates normally; battery voltage remains above lower limit |
| Charge/Discharge Endurance Test | Ensure safety under long-cycle operation | No safety incidents during cycling |
| Dielectric Voltage Withstand Test | Verify electrical insulation strength | No breakdown or flashover |
Functional Safety AssessmentUL 1973:2022 adds formal functional safety evaluation, adopting principles from IEC 61508 / ISO 26262 to audit hardware and software safety functions of the Battery Management System (BMS).
EMC Electromagnetic Compatibility RequirementsThe 2022 edition introduces mandatory EMC testing, ensuring stable operation under electromagnetic interference and preventing unacceptable interference to surrounding equipment.
表格
| Standard No. | Standard Name | Application |
|---|---|---|
| UL 1973:2022 | Safety Standard for Stationary Energy Storage Batteries | Cell, module and battery system safety |
| UL 9540:2024 | Safety Standard for Energy Storage Systems and Equipment | Integrated ESS including PCS system safety |
| UL 9540A | ESS Thermal Runaway Flame Propagation Test | Thermal spread assessment at cell / module / unit / installation level |
| IEEE 1547:2018 | Standard for Interconnection and Interoperability of Distributed Energy Resources | ESS grid interconnection technical requirements |
| NFPA 855 | Standard for the Installation of Energy Storage Systems | Installation spacing, fire protection and site safety rules |
Guangdong Energy Storage Testing Technology provides professional UL 1973:2022 testing and certification services for energy storage manufacturers. We fully understand North American market access barriers and compliance complexity, offering full technical compliance support:
A:
A:UL 1973 focuses on the safety of the battery itself (cell → module → battery system).UL 9540 covers the overall integrated energy storage system including PCS, BMS and thermal management.Stationary ESS entering North America generally need to comply with both standards.
A:It focuses on BMS hardware and software safety functions, including safety target definition, FMEA analysis, and software safety integrity level evaluation. Enterprises shall sort out the BMS safety architecture in advance and prepare FMEA reports and functional safety manuals.
A:Four core items: conducted emission, radiated emission, conducted immunity and radiated immunity. The new EMC clause is mandatory in the 2022 edition, requiring early EMC design reservation during product development.